Acid cleaning
Many methods are used by different boiler makers to clean the mill scale and rust inside the tube surface. It is very important that this operation is carried out by an experienced and reliable agency. The methods used are circulating acid method and soaking method.
In the case of the circulating method, external acid cleaning pumps are used to keep the acid in circulation. However in the case of soaking method the acid is kept stationary for a specified time. Many combinations of acids are used for this purpose. The most popular acid is 5% hydrochloric acid with inhibitors that are used to inhibit the action of acid on the cleaned surface of the tube. The super heater tubes should be plugged and water filled and maintained under positive pressure so that the acid vapors do not enter the tube surface. The boiler is drained under nitrogen at a positive pressure; this is needed to protect the internal virgin surface. The sludge resulting from mill scales and rust will have to be flushed from the bottom headers. The boiler then goes though a passivation operation to ensure a protective layer formation inside the tube surface.
Steam blowing
Steam blowing is used to clean the super heater coils and the steam pipes like main steam and reheater pipes. There are two methods used for steam blowing: continuous blowing and intermittent blowing. In both cases, the idea is to create a disturbance on the surface of the tube or pipe well above that is possible during the peak load operation of the boiler. It is seen that at a pressure of around 40 kg/cm squared, the internal surface of the super heater and steam pipes are subjected to such a disturbance that any loosely adhering material is dislodged when the steam is allowed to blow out to the atmosphere. The completion of steam blowing is declared if the target plate of turbine blade material kept at the predefined point is free from any indentation or is within allowed limits. To complete the steam blowing in super heater, reheater, steam pipes, etc, steam blowing is done in more than one stage.
Post-operational cleaning
During operation boilers accumulate deposits inside the tube surface depending upon the quality of water chemistry maintained. Once the boilers have operated for about five years then it is a good practice to take tube samples from the high heat flux region and evaluate them for internal deposit. The samples are taken from all the four walls of the boiler furnace walls and tested for the amount of deposit and the chemistry of deposit. If the deposit quantity is above 40 mg/cm squared, then the tube is termed dirty and acid cleaning is recommended. The type of acid to be used for cleaning will depend upon the chemistry and adherence of the deposits to the tube surface. If the deposit contains copper from the pre-boiler system, then this has to be first removed. The other ingredients of the deposit are removed subsequently. Hence the post operational cleaning can have a few stages of acid cleaning. To decide this, tube samples taken are subjected to a cleaning test in the lab using the actual acid, temperature, time and stages planned at the site. Based on the results of the cleaning in the lab and result there achieved, the final recommendation is given to the boiler owner.